Used for cleanrooms and operating rooms
The HEPA filters are checked for leak proofness at the end of the production process. It is advised to validate the functioning of the air-handling units after installation of the new HEPA filters, because of possible damages during transport or installation.
Application: cleanrooms, operating rooms
Frame: extruded aluminum
Spacers: Hotmelt
Bonding: 2 component polyurethane
Media: glasfibre paper
Gasket: frothed polyerethane
Filter Classification according to EN1822: H13, H14
Maximum/recommended final pressure drop: 500 Pa
Maximum temperature: 70°C
Maximum relative humidity: 90%
Type | Dimensions WxHxD (mm) | Filter Classification | Airflow (m3/h) | Airflow (L/s) | Pressure Drop (Pa) | Filter surface (m2) |
---|---|---|---|---|---|---|
HLA1113DBBL | 305 x 305 x 150 | H13 | 150 | 41 | 120 | 2.7 |
HLA1113DBEL | 305 x 610 x 150 | H13 | 300 | 83 | 120 | 5.5 |
HLA1114DBBL | 305 x 305 x 150 | H14 | 150 | 41 | 140 | 2.7 |
HLA1114DBEL | 305 x 610 x 150 | H14 | 300 | 83 | 140 | 5.5 |